Sales
Support
1800-123-8786
ONLINE TRANSFORMER BASED UPS
10 KVA ~ 120 KVA ( 3:3 PHASE 0.9 PF )

Download our complete brochure

We are a world class manufacturer and exporter of Power Conditioning Solutions providing the best quality products and services to our customers.

ASTRO series UPS is a Smart 3 phase in 3 phase out uninterruptible power supply, it adopts double transform high frequency SPWM and high-performance digital signal processor precision design, meets all high reliability requirements of UPS and integrates reliability, safety, maintainability of a new generation low frequency UPS.

Features
Online double-conversion with full DSP control
IGBT inverter with output isolation transformer
100% unbalance load capability
Output power factor 0.9
Generator compatible
Auto-restart
Green mode function ensure optimize efficiency to save energy
Touch screen display, friendly human & machine interface
Intelligent self-diagnosing function, all kinds of failure protection
More then 10000 events and history recode
High MTBF (> 200,000 h) & Low MTTR (< 0.4 h)
(EPO) Emergency Power Off function
Versatile Communication RS232,RS485,dry contacts communication port
Optional SNMP & dry contract
Optional N+X redundancy parallel up to 6 units
ASTRO SERIES

10 Kva ~ 120 kva ( 3:3 phase 0.9 pf )

SPECIFICATIONS
MODEL ASTRO3310T30 ASTRO3315T30 ASTRO3320T30 ASTRO3330T30 ASTRO3340T30 ASTRO3360T30 ASTRO3380T30 ASTRO33100T30 ASTRO33120T30
Capacity 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA
INPUT
Rated Voltage 380 / 400 / 415 Vac ± 25%
Voltage Range 110 ~ 176 Vac (Load Dependent and 100% load ); 176 ~ 290 V
Frequency 50 ~ 60 Hz (auto-sensing)
Eco Voltage Range ± 10% (settable)
Bypass Voltage Range ± 20% (settable)
OUTPUT
Voltage 380 / 400 / 415 Vac
Voltage regulation ±1%
Frequency 50 / 60 Hz ± 2.5 Hz (battery mode)
Waveform Pure Sinusoidal Waveform
Power factor 0.9
Total harmonic distortion (THDv) ≤ 2% (linear load)
Crest factor 3:1
Overload ≤ 110% for 60 Mins, ≤ 125% for 10 min, ≤ 150% for 60 sec, ≤ 200% for 100 msec
BATTERIES
DC voltage 360 Vdc (360 ~ 384 settable)
Inbuilt battery 30 Nos (30 ~ 32 settable)
Charging current (standard) 20% (default), settable
Recharging topology Charging Three-stage charging, auto switch floating / equalizing charge
Battery self-test Battery self-test Settable periodic self-test; manually configurable test time and voltage
SYSTEM
Efficiency ≤ 94% at 100% load, 98% in ECO mode
Max. number of parallel connections 6
Protections Short-circuit, overload, overtemperature, battery discharge protection and fan testing protection
Communications RS232 (standard), USB / RS485 / dry contacts / SNMP (optional)
Display LCD + LED
Standards EN 62040-1, EN 62040-2, EN 61000-3-2, EN 61000-3-3, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2, IEC 62040-2, IEC 62040-1, IEC 62040-3
OTHERS
Operating temperature 00C ~ 450C
Storage temperature -250C ~ 550C (without batteries)
Relative Humidity 0 ~ 95% (non-condensing)
Altitude ≤ 1500 m, derating 1% for each additional 100 m
IP rating IP 20
Noise level at 1m ≤ 55 dB ≤ 60 dB ≤ 65 dB
Dimensions (WxDxH) (mm) 400 x 800 x 1100 450 x 860 x 1200 640 x 800 x 1500 700 x 800 x 1700
Net weight (kg) 145 kg 155 kg 160 kg 210 kg 240 kg 300 kg 485 kg 610 kg 670 kg
Gross weight (kg) 175 kg 185 kg 190 kg 240 kg 270 kg 330 kg 515 kg 640 kg 700 kg